A time-of-day (ToD) tariff charges different rates for electricity at different hours. In Karnataka, HT commercial and industrial consumers already face higher charges in defined peak hours, and a battery storage system can charge when power is cheaper or comes from your own solar and discharge in those peak hours. The saving comes from the price gap, so the exact tariff in your latest bill is what matters.
What is a ToD tariff?
A ToD tariff splits the day into slots, typically peak, normal and solar (daytime) or off-peak hours, and applies a different energy charge to each. The idea is to encourage consumers to move load away from the hours when the grid is under most stress.
At the national level, the Electricity (Rights of Consumers) Amendment Rules, 2023 require ToD tariffs for commercial and industrial consumers with a maximum demand of 10 kW and above. Under the rules, solar-hour tariffs are set 10 to 20 per cent below the normal tariff while peak-hour tariffs are 10 to 20 per cent higher (opens in a new tab), with solar hours defined as an eight-hour window set by the State Commission. Peak hours cannot be longer than solar hours.
ToD in Karnataka
The Karnataka Electricity Regulatory Commission (KERC) has applied ToD to HT consumers for several years. In its FY2024-25 order, KERC introduced a morning peak from 6 am to 9 am in addition to the existing evening peak from 6 pm to 10 pm (opens in a new tab). KERC then approved a three-year retail tariff for 2025-26, 2026-27 and 2027-28 (opens in a new tab) for all distribution licensees (BESCOM, MESCOM, CESC Mysore, HESCOM and GESCOM), including a 30 paise per unit reduction in HT industrial energy charges in 2025-26 (opens in a new tab).
Tariff orders, ToD adders and demand charges are revised from time to time, and licensees can also recover true-up amounts. Always take the peak, normal and off-peak rates from your latest bill or the current KERC order for your ESCOM before sizing a battery.
Tariffs change; always check your latest bill and the current KERC order.
How a battery uses the tariff gap
- Charge during the cheaper window: from your rooftop solar in the day, or from the grid in off-peak hours, subject to your tariff slots.
- Discharge during the peak slots, so the factory draws less from the grid when units are most expensive.
- Repeat every working day. The annual saving scales with how many kWh you shift and how large the price gap is.
A system with 0.5P rating, such as the 125 kW / 261 kWh TCL BlueArk W10, can deliver its rated power for about two hours, which suits a part of the evening peak. Four-hour peak windows are served by larger energy capacity, by two cabinets, or by a 0.25P block.
Illustrative savings (hypothetical)
Suppose a battery shifts 200 kWh into the peak slot on 300 working days a year, which is 60,000 kWh. The gross saving depends on the net price gap per kWh, meaning the peak rate minus the effective cost of the energy used to charge, including losses.
| Net gap (₹ per kWh) | Annual saving before O&M |
|---|---|
| ₹1 | ₹60,000 |
| ₹2 | ₹1,20,000 |
| ₹3 | ₹1,80,000 |
| ₹4 | ₹2,40,000 |
Illustrative only: 200 kWh shifted on 300 working days (60,000 kWh a year). Not a prediction.
These are not predictions. They show how the result scales with the price gap and with how often the battery cycles. Your own bills decide where you sit in the table, and the battery's cost, life and degradation decide the payback. Demand-charge savings from peak shaving may add to this where your load profile allows.
Charging from solar makes the gap wider
The cheapest energy for charging is often your own solar. A rooftop or ground-mounted plant can charge the battery through the day, and the stored energy then displaces peak-slot grid purchases. An all-in-one hybrid cabinet such as the TCL BlueArk X5 combines a PV inverter, PCS and battery, which can simplify this on new projects. See solar plus storage.
Checklist before you decide
- Which ToD slots and rates apply to your tariff category today?
- What are your peak-slot kWh on a typical working day (from interval data)?
- Do you have solar, or enough off-peak hours to recharge?
- How many days a year will the battery cycle?
- What are your demand charge and contract demand?
- Is there space and safe access for an outdoor cabinet?
Talk to Nexera
Send your latest HT bill and a month of interval data, and Nexera will check whether a ToD-led battery makes sense for your site. Request a ToD savings check or partner with Nexera as an EPC company.